Skip to content
Direct Driven

Dry Mounted Pumps

Diesel Direct Driven Horizontal Dry Mounted Pump with Accessories 

Our compact, cost-efficient, and robust fire water pump solution is built for standby use in offshore and marine environments. The system utilizes Eureka’s BB2 pump, engineered in full compliance with NFPA 20 and API 610 standards. The system is fully self-contained, requiring no external utilities. Its simple mechanical design ensures high reliability, low power consumption, and minimal maintenance. 

Direct Diesel Driven FW Pump w/Eureka BB2 Pump Configurations

Main Features & Benefits

  • Simple and cost-effective API 610 firewater pump system  
  • Low system complexity with few components and direct drive. 
  • No limitations in capacity or power range 
  • Compact layout, minimizes space requirements 
  • High pump efficiency and low power demand 
  • Low weight, reducing material needs, and CO₂ emissions 
  • All maintenance required elements above sea level 
  • Simple, robust mechanical design with direct drive 
  • Proven operational reliability in demanding offshore conditions 

Description

The fire water pump is a dry mounted single or double suction single-stage centrifugal pump in a horizontal version for standby operation. 

The system consists of a horizontal single or double-suction, single-stage centrifugal pump directly driven by a high-speed, turbocharged diesel engine. The cooling system draws water from the pump discharge, eliminating the need for external cooling sources. Power is transmitted via a flexible shaft coupling, allowing smooth engine operation and easy alignment. 

All components are mounted on a heavy-duty skid with an integrated drip pan. A PLC-based NFPA 20 control system ensures safe and automated operation. The design is optimized for low complexity and quick access to all maintenance areas. 

Learn More About the BB2 Pump 

Diesel Engine 

  • Type: High-speed, direct injection, turbocharged marine diesel 
  • Duty Rating: 12–24 hours continuous + 10% overload 
  • Cooling: Self-contained, T-off from pump discharge for water supply 
  • Control System: PLC-based, NFPA 20 compliant